Αισθητήρας VOC με ψηφιακές και αναλογικές εξόδους.
Standard code |
|
CAP1160 |
Measurement principle |
|
Micro-machined metal oxide semiconductor (MOS) technology |
Working range |
CO2 eq |
0…2 000 ppm |
Measurement reporting interval |
s |
60 |
Supply voltage |
VDC |
12 VDC +/- 10 % |
Average power consumption |
A |
40 mA |
Max. peak current |
A |
1 (use for fuse sizing) |
Enclosure Protection |
|
IP 20 |
Storage conditions |
|
-25…50°C 5…95 % RH (without condensation) 85…110 kPa |
Working conditions |
|
0…50°C 5…95 % RH (without condensation) 85…110 kPa |
PWM digital output |
|
|
Output data |
|
0 to 100 % 0 % = 0 ppm CO2 eq ; 100 % = 2 000 ppm CO2 eq |
Voltage |
VDC |
12 VDC +/- 10 % |
Frequency |
KHz |
1 |
Output 0-10 V (analog) |
|
|
Output data |
|
0 to 10 V 0 V = 0 ppm CO2 eq ; 10 V = 2 000 ppm CO2 eq |
Voltage |
V |
0 to 10 |
Required impedence |
Ω |
>1M |
Characteristics |
|
|
Weight |
g |
80.5 |
Colour |
|
white |
Material |
|
ABS |