Η φορητή αυτόνομη λύση της Thermokon, NOVOS 3, απλοποιεί την παρακολούθηση της ποιότητας του αέρα εσωτερικού χώρου και είναι σε θέση να λάβει τα απαραίτητα μέτρα για τη βελτίωση της ποιότητας του αέρα.
Specifications / Models | NOVOS 3 CO2+VOC | NOVOS 3 CO2 | NOVOS 3 VOC |
---|---|---|---|
Measured values | CO2, VOC, temperature + humidity (depending on the device), each output can be set to get a variable mix of CO2 and VOC by configuration | CO2, temperature + humidity (depending on the device) | VOC, temperature + humidity (depending on the device) |
Output voltage | VV: 2x 0..10 V, 3xV: 3x 0..10 V, 4xV: 4x 0..10 V, 0..10 V or 0..5 V (live-zero can be configured via app or uConfig), min. load 10 kΩ | V: 1x 0..10 V, VV: 2x 0..10 V, 3xV: 3x 0..10 V, 0..10 V or 0..5 V (live-zero can be configured via app or uConfig), min. load 10 kΩ | V: 1x 0..10 V, VV: 2x 0..10 V, 3xV: 3x 0..10 V, 0..10 V or 0..5 V (live-zero can be configured via app or uConfig), min. load 10 kΩ |
Output current | AA: 2x 4..20 mA, 3xA: 3x 4..20 mA, 4xA: 4x 4..20 mA, max. load 500 Ω | A: 1x 4..20 mA, AA: 2x 4..20 mA, 3xA: 3x 4..20 mA, max. load 500 Ω | A: 1x 4..20 mA, AA: 2x 4..20 mA, 3xA: 3x 4..20 mA, max. load 500 Ω |
Network technology | RS485 BACnet (MS/TP), RS485 Modbus | BACnet MS/TP, RS485 Modbus | RS485 BACnet (MS/TP), RS485 Modbus |
Power supply | 15..35 V = or 19..29 V ~ SELV, AA | 3xA | 4xA:, 15..35 V = SELV | 15..35 V = or 19..29 V ~ SELV, A | AA | 3xA:, 15..35 V = SELV | 15..35 V = or 19..29 V ~ SELV, A | AA | 3xA:, 15..35 V = SELV |
Measuring range humidity | 0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app, uConfig or BUS | 0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app, uConfig or BUS | 0..100% rH non-condensing, enthalpy: 0..85 KJ/kg, absolute humidity: 0..50 | 0..80 g/m³, dew point: 0..+50 | -20..+80 °C, optionally configurable via app, uConfig or BUS |
Measuring range CO2 (for models CO2+VOC and CO2) | 0..2000 ppm | 0..5000 ppm, optionally configurable via app, uConfig or BUS | 0..2000 ppm | 0..5000 ppm, optionally configurable via app, uConfig or BUS | N/A |
Accuracy temperature | ±0,5 K (typ. at 21 °C) | ±0,5 K (typ. at 21 °C) | ±0,5 K (typ. at 21 °C) |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) | ±2% between 10..90% rH (typ. at 21 °C) | ±2% between 10..90% rH (typ. at 21 °C) |
Accuracy CO2 (for models CO2+VOC and CO2) | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa) | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa) | N/A |
Calibration | self-calibration, CO2: Dual Channel | self-calibration, Dual Channel | self-calibration |
Sensor | VOC sensor (heated metal oxide semiconductor), CO2: NDIR (non-dispersive, infrared) | NDIR (non-dispersive, infrared) | VOC sensor (heated metal oxide semiconductor) |
Inputs | RS485 Modbus:, 1x input for floating contact | RS485 Modbus:, 1x input for floating contact | RS485 Modbus:, 1x input for floating contact |
Display | RGB-LED indicating air quality (traffic light function ‘TLF’), optional | RGB-LED indicating air quality (traffic light function ‘TLF’), optional | RGB-LED indicating air quality (traffic light function ‘TLF’), optional |
Colour | pure white, black or aluminium | pure white, black or aluminium | pure white, black or aluminium |
Enclosure | PC V0, optionally with design cover black or aluminium | PC V0, optionally with design cover black or aluminium | PC V0, optionally with design cover black or aluminium |
Protection (IP) | IP20 according to EN 60529 | IP20 according to EN 60529 | IP20 according to EN 60529 |
Cable entry | rear entry, breaking points bottom, drill mark top | rear entry, breaking points bottom, drill mark top | rear entry, breaking points bottom, drill mark top |
Electrical connection | tool-free mountable spring clamp, max. 1,5 mm² | tool-free mountable spring clamp, max. 1,5 mm² | tool-free mountable spring clamp, max. 1,5 mm² |
Ambient condition | 0..+50 °C, max. 85% rH non-condensing | 0..+50 °C, max. 85% rH non-condensing | 0..+50 °C, max. 85% rH non-condensing |
Mounting | flush-mounted on standard EU box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately | flush-mounted on standard EU box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately | flush-mounted on standard EU box (Ø=60 mm), or to be mounted flat onto the surface using screws, base part can be mounted and wired separately |
Notes | for configuration an optional programming dongle (Bluetooth) is available (refer to accessories), mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...) | for configuration an optional programming dongle (Bluetooth) is available (refer to accessories) | for configuration an optional programming dongle (Bluetooth) is available (refer to accessories), mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...) |